Laser Extraction Ductwork Replacement and LEV Retesting

When testing identifies a problem that servicing alone cannot solve

An extraction system can be running while still having faults that need attention. In this laser-cutting project, an initial LEV examination recorded an unsatisfactory assessment. The findings helped define the remedial work, followed by a further examination after the work.

What the initial examination found

During the initial assessment, the extraction was not effectively controlling fumes from the laser-cutting process. The report also recorded leakage at multiple spiral-ductwork joints, a loose connection at the extraction unit and inadequate ductwork support. Some joints had been taped in an attempt to reduce leakage.

The inspection identified incorrectly fitted filters, including a visible gap that could allow dust bypass. Filters and a smoke alarm were replaced during the initial visit, and cleaning settings were adjusted. These servicing actions did not change the report’s overall unsatisfactory assessment.

Attending to the extraction unit does not automatically resolve problems elsewhere in the ductwork system.

The remedial work

Premier LEV carried out the work as part of a project delivered through an equipment supplier. The remedial scope included replacing the existing spiral ductwork with clip-together ductwork and replacing the poor supports.

The work addressed physical installation issues identified during the earlier visit. A follow-up LEV examination provided a separate record of the system’s assessed performance after the remedial work.

The recorded outcome

The initial report recorded an unsatisfactory assessment. The laser was operating during the subsequent retest, and the follow-up report recorded a satisfactory assessment.

These are the outcomes recorded in the project reports. They should be understood within the scope and limitations of each examination; they are not a claim that all workplace exposure risks were eliminated.

What other employers can learn

  • Check the whole extraction system, including joints, connections and supports.

  • Use examination findings to define the remedial work needed.

  • Keep servicing records alongside the examination reports.

  • Arrange appropriate checks following alterations or repairs.

  • Review the report’s limitations as well as its overall conclusion.

Dust deposits around the original extraction duct connection before remedial work

Before: dust deposits around the original duct connection, photographed during the initial visit.

Replacement clip-together extraction ductwork secured with a collar and support rod

After: replacement clip-together ductwork and its support arrangement.

Need help with an unsatisfactory LEV report?

Premier LEV provides LEV testing and examination, servicing and remedial support, and system installation.

Send your enquiry with details of your extraction system, the reported defects and any previous examination records so we can discuss the next steps.